Anandji Cables - Simplifying Electronics
NILSON - PVC Insulated Wires And Cables
Home About Us Products Clients Downloads Contacts
L. T. CONTROL CABLES
TECHNICAL CURRENT RATINGS
TABLE III (POWER CABLES/ Multi Core)
2 Core, 3 Core and 4 Core Copper Conductor, PVC Insulated, PVC Sheathed, Unarmoured (YY)/ Armoured (YWY and YFY) Cables - 650/ 1100 Volts.
No. of Cores Nom. Cross Sectional Area (sq. mm.) Nom. Thickness of PVC Insulation (mm) Minimum thickness of Inner Sheath (mm) Unarmoured Armoured Max. DC conductor Resistance at 20o C (ohm/ km) AC Current Ratings
Approx. Overall Dia. (mm) Approx. Net Weight (kg/ km) Nom steel Armour (mm) Approx. Overall Dia. (mm) Approx. Net Weight (kg/ km) Ground Amps Air Amps
W F
2 4.00 1.0 0.3 13.3 260 1.4   16.3 590 4.16 41 35
2 6.00 1.0 0.3 14.3 325 1.4 17.2 690 3.08 50 45
2 10.00 1.0 0.3 16.0 440 1.4 19.0 860 1.83 70 60
2 16.00 1.0 0.3 19.5 660   4x0.8 21.0 1000 1.15 90 78
3 4.00 1.0 0.3 14.0 310 1.4   16.9 670 4.61 36 30
3 6.00 1.0 0.3 15.2 395 1.4 18.0 775 3.08 45 39
3 10.00 1.0 0.3 17.0 540   4x0.8 20.1 1020 1.83 60 52
3 16.00 1.0 0.3 20.6 820 4x0.8 22.3 1190 1.15 77 66
4 4.00 1.0 0.3 15.0 370 1.4   18.1 760 4.61 36 30
4 6.00 1.0 0.3 16.5 485   4x0.8 19.4 920 3.08 45 39
4 10.00 1.0 0.3 18.5 675 4x0.8 20.8 1110 1.83 60 52
4 16.00 1.0 0.3 22.7 1030 4x0.8 24.4 1435 1.15 77 66
* Cables with stranded conductor can be made on request.