Anandji Cables - Simplifying Electronics
NILSON - PVC Insulated Wires And Cables
Home About Us Products Clients Downloads Contacts
L. T. CONTROL CABLES
TECHNICAL CURRENT RATINGS
TABLE II (2.5 sq. mm.)
Solid Copper Conductor, PVC Insulated, PVC Sheathed, Unarmoured (YY)/ Armoured (YWY and YFY) Multi Core Control cables - 650/ 1100 Volts.
No. of Cores Nom. Thickness of PVC Insulation (mm) Minimum thickness of Inner Sheath (mm) Unarmoured Armoured Max. DC conductor Resistance at 20o C (ohm/km) AC Current Ratings
Approx. Overall Dia. (mm) Approx. Net Weight (kg/ km) Nom steel Armour (mm) Approx. Overall Dia. (mm) Approx. Net Weight (kg/ km) Ground Amps Air Amps
W F
2 0.9 0.3 11.75 180 1.4   14.8 452 7.41 32 27
3 0.9 0.3 12.35 215 1.4 15.5 499 7.41 27 24
4 0.9 0.3 13.30 260 1.4 16.4 571 7.41 27 24
5 0.9 0.3 14.5 305 1.4 17.4 690 7.41 23 19
6 0.9 0.3 15.50 360 1.4 18.5 732 7.41 21 18
7 0.9 0.3 15.50 380 1.4 18.5 752 7.41 20 17
8 0.9 0.3 16.75 432   4x0.8 19.55 829 7.41 19 16
9 0.9 0.3 18.50 490 4x0.8 20.2 850 7.41 19 16
10 0.9 0.3 19.20 530 4x0.8 21.9 876 7.41 18 15
12 0.9 0.3 20.30 610 4x0.8 22.3 952 7.41 17 14
14 0.9 0.3 21.20 690 4x0.8 24.0 1061 7.41 16 13
16 0.9 0.3 22.30 770 4x0.8 25.0 1172 7.41 15 13
19 0.9 0.3 23.35 875 4x0.8 26.0 1283 7.41 14 12
24 0.9 0.3 26.70 1090 4x0.8 30.0 1556 7.41 13 11
27 0.9 0.3 27.50 1190 4x0.8 30.5 1680 7.41 12 10
30 0.9 0.3 28.50 1310 4x0.8 31.5 1857 7.41 12 10
37 0.9 0.3 31.30 1610 4x0.8 34.0 2138 7.41 11 9
44 0.9 0.3 34.0 1960 4x0.8 36.5 2500 7.41 10 9
52 0.9 0.3 37.0 2300 4x0.8 38.5 2900 7.41 10 8
61 0.9 0.3 39.5 2600 4x0.8 40.0 3300 7.41 9 8
* Cables with stranded conductor can be made on request.