TABLE I (1.5 sq. mm.)
Solid Copper Conductor, PVC Insulated, PVC Sheathed, Unarmoured (YY)/ Armoured (YWY and YFY) Multi Core Control cables - 650/ 1100 Volts.
No. of Cores Nom. Thickness of PVC Insulation (mm) Minimum thickness of Inner Sheath (mm) Unarmoured Armoured Max. DC conductor Resistance at 20o C (ohm/ km) AC Current Ratings
Approx. Overall Dia. (mm) Approx. Net Weight (kg/ km) Nom steel Armour (mm) Approx. Overall Dia. (mm) Approx. Net Weight (kg/ km) Ground Amps Air Amps
W F
2 0.8 0.3 10.5 137 1.4   13.8 371 12.1 23 20
3 0.8 0.3 11.0 160 1.4 14.0 406 12.1 21 17
4 0.8 0.3 11.85 189 1.4 15.0 416 12.1 21 17
5 0.8 0.3 12.80 224 1.4 15.7 550 12.1 16 14
6 0.8 0.3 13.60 259 1.4 16.6 580 12.1 15 13
7 0.8 0.3 13.60 271 1.4 16.6 593 12.1 14 13
8 0.8 0.3 15.60 293 1.4 17.65 641 12.1 14 13
9 0.8 0.3 16.00 340 1.4 18.7 680 12.1 13 11
10 0.8 0.3 16.50 373 1.4 20.0 800 12.1 13 11
12 0.8 0.3 17.30 439   4x0.8 20.2 858 12.1 12 10
14 0.8 0.3 18.00 481 4x0.8 20.9 796 12.1 11 10
16 0.8 0.3 19.00 554 4x0.8 21.6 880 12.1 11 9
19 0.8 0.3 20.30 609 4x0.8 22.5 935 12.1 10 9
24 0.8 0.3 23.30 758 4x0.8 25.4 1162 12.1 9 8
27 0.8 0.3 23.80 820 4x0.8 25.8 1240 12.1 9 8
30 0.8 0.3 24.60 896 4x0.8 26.6 1327 12.1 9 7
37 0.8 0.3 26.20 1071 4x0.8 29.0 1527 12.1 8 7
44 0.8 0.3 30.0 1150 4x0.8 31.0 1650 12.1 7 6
52 0.8 0.3 32.0 1360 4x0.8 33.0 1800 12.1 7 6
61 0.8 0.3 34.0 1680 4x0.8 34.5 2250 12.1 6 6
* Cables with stranded conductor can be made on request.