Anandji Cables - Simplifying Electronics
NILSON - PVC Insulated Wires And Cables
Home About Us Products Clients Downloads Contacts
NILSON FLEXIBLE CABLES IS : 694
TECHNICAL DATA FOR FLEXIBLE CABLES
NILSON PVC Insulated Flexible Single and Multicore Cables, manufactured with bright annealed bare copper conductor as per IS:8130/1976 Table 14, Class V for Flexible use insulated with Di-electric grade PVC Compound and or PVC Sheathed impervious to oil, water, petrol, acids and greases as per latest IS specifications IS:694/1977 for working voltage up to and including 1100 Volts.
CONDUCTOR INSULATION SHEATH
THICKNESS
OVERALL
DIAMETER
AREA
(Sq. mm.)
No. & Size of Wire Diameter Max Resistance
@ 20o C
Current DC OR 1 OR 3 Nominal Thickness Nominal (mm) Maximum (mm)
      S.C. M.C.     1 Core 2 Core 3 Core 4 Core 1 Cr SCSH TF SH 2 Cr RD 3 Cr RD 4 Cr RD
mm mm mm Ohms / KM Amps mm mm mm mm mm mm mm mm mm mm mm
0.50 16/ .2 0.94 37.10 39.0 4 0.6 0.9 0.9 0.9 0.9 2.30 4.20 4.2 * 6.5 6.50 6.85 7.45
0.75 24/ .2 1.20 24.70 26.0 7 0.6 0.9 0.9 0.9 0.9 2.55 4.45 4.45 * 7 7.00 7.40 8.05
1.00 32/ .2 1.34 18.50 19.5 11 0.6 0.9 0.9 0.9 0.9 2.70 4.60   7.30 7.75 8.45
1.50 48/ .2 1.64 12.70 13.3 14 0.6 0.9 0.9 0.9 0.9 2.95 4.85   7.80 8.25 9.25
2.50 80/ .2 2.08 7.60 7.98 19 0.7 1.0 1.0 1.0 1.0 3.65 5.75   9.40 10.0 10.95
4.00 56/ .3 2.61 4.71 4.95 26 0.8 1.0 1.0 1.0 1.0 4.35 6.50   10.75 11.5 12.65
TECHNICAL DATA FOR HEAVY DUTY FLEXIBLE CABLES
NILSON PVC Insulated Heavy duty Flexible Single Core Cables, manufactured with bright annealed bare copper conductor as per IS:8130 for Flexible use insulated with extra thick Di-electric grade PVC Compound impervious to oil, water, petrol, acids and grease as per Latest IS specification IS:694 for working voltage 650/1100 Volts.